Upon call out to review previous contractors install we noted the following
- Condensing unit had no refrigerant charge in system
- Copper lineset connections were hand tight
- Electrical serving the indoor units was improperly installed and not to code
- Exterior install of piping and wiring was less than acceptable
- Units were not running and not operational the way they were left
Work done to remedy the situation
- Replace copper linesets as there was no way of determining their integrity
- Run new drains down to grade level (current drains were stubbed out of soffit)
- Install Fortress covering to hide copper linesets within
- Run test and commission and add necessary refrigerant charge for the system to operate correctly
*Seperate call out to replace faulty furnace ignitor included in costs.