Quote

From:

1-13819 232nd Street
Maple RIdge, BC, V4R0C7
Ph: 778-833-3473

info@cands.ca

Quote Number QUO-11267
Quote Date May 7, 2021
Total $111,090.00
To:
Elevation Building Solutions

PAELLA GUYS HVAC QUOTATION

SUPPLY AND INSTALL THE FOLLOWING:

 

- NFPA GREASE WELDED GREASE DUCT

- MUA DUCTING FROM ROOF TO HOODS

 

(H1)

Wallmount grease exhaust hood built to NFPA96 standards

Constructed with solid 18 gauge stainless steel on all surfaces

430 #4 Finish

Length: 107'' - Depth: 57'' - Height: 30''

Captrate Solo high efficiency stainless steel baffle grease filters

cULus certified

NSF certified

Accessories:

• 3” stainless steel spacer integrated to the rear of the hood to respect the clearance required for

semi-combustible materials according to NFPA96 Qty: 1

• Grease bucket for hood Qty: 1

• Hanging brackets (4x) Qty: 1

• Recessed LED Light fixture with 1150 total lumens supplying a warm 3000K color temperature,

perfect for food applications. Meets all requirements of NFPA 96 and cULus and NSF listed. Qty: 2

• ULc 1” stainless steel spacer integrated to the left side of the hood with 1” of thermal

insulation to respect the clearance required for semi-combustible and combustible materials. Qty:

1

• ULc 3” stainless steel spacer integrated to the rear of the hood with 1” of thermal insulation to

respect the clearance required for semi-combustible and combustible materials. Qty: 1

• Welded exhaust collar Qty: 1

 

(P1)

Downdischarge stainless steel perforated supply plenum

Length: 108″ Width: 18″ Height: 6″

Accessories :

Supply collar with balancing damper Qty: 2

Hanging brackets for plenum 3’-12’ Qty: 1

 

(H2)

Wallmount grease exhaust hood built to NFPA96 standards

Constructed with solid 18 gauge stainless steel on all surfaces

430 #4 Finish

Length: 174'' - Depth: 57'' - Height: 30''

Captrate Solo high efficiency stainless steel baffle grease filters

cULus certified

NSF certified

Accessories:

• 3” stainless steel spacer integrated to the rear of the hood to respect the clearance required for

semi-combustible materials according to NFPA96 Qty: 1

• Grease bucket for hood Qty: 2

• Hanging brackets (6x) Qty: 1

• Recessed LED Light fixture with 1150 total lumens supplying a warm 3000K color temperature,

perfect for food applications. Meets all requirements of NFPA 96 and cULus and NSF listed. Qty: 3

• Sturdy 18G stainless steel free standing insulated panel 1” thick with adjustable bullet feet.

RIGHT SIDE Qty: 1

• ULc 3” stainless steel spacer integrated to the rear of the hood with 1” of thermal insulation to

respect the clearance required for semi-combustible and combustible materials. Qty: 1

• Welded exhaust collar Qty: 2

(P2)

Downdischarge stainless steel perforated supply plenum

Length: 174″ Width: 18″ Height: 6″

Accessories :

Supply collar with balancing damper Qty: 3

Hanging brackets for plenum 13’-16’ Qty: 1

(FS-1 FIRE SUPRESSION)

ANSUL 3+3+3 Gallons Gas

ANSUL 3+3+3 gallon (33 pts max)fire suppression system pre piped in the hood. Includes

stainless steel piping, stainless steel cabinet, remote manual pull station, double microswitch and

gas valve. FINAL FIELD HOOK UP NOT INCLUDED

Cartridge and chemical: 1

 

(KEF-1)

FKUD180 High Speed Direct Drive Centrifugal Upblast Exhaust Fan with, disconnect switch and 18

-3/4" wheel.

Exhaust Fan handles 1881 CFM @ -1.000" wc ESP, Fan runs at 948 RPM.

Exhaust Motor: 1.000 HP, 3 Phs, 208 V, 60Hz, 3.8 FLA, ODP, Premium (E-Plus3) Eff.

Accessories :

• Grease Cup for kitchen-duty centrifugal exhaust fans, Box Dimensions 17-1/8 L X 5-1/16 W X 3

-3/4 H (18 GA.) (Includes Down Spout)

• FKUD180 Curb CRB26.5x24 HIGH vented

• HINGE KIT - Standard Hinge kit for exhaust fan roof curbs. Includes Hardware to attach hinge to

curb and hinge to base. Ships Loose. Used on Fans with wheels 20 inches or smaller. 12 GA

Galvanized.

 

(KEF-2)

FKUD180 High Speed Direct Drive Centrifugal Upblast Exhaust Fan with, disconnect switch and 18

-3/4" wheel.

Exhaust Fan handles 2900 CFM @ -1.000" wc ESP, Fan runs at 1124 RPM.

Exhaust Motor: 3.000 HP, 3 Phs, 208 V, 60Hz, 9.5 FLA, ODP, Premium (E-Plus3) Eff.

Accessories :

• Grease Cup for kitchen-duty centrifugal exhaust fans, Box Dimensions 17-1/8 L X 5-1/16 W X 3

-3/4 H (18 GA.) (Includes Down Spout)

• FKUD180 Curb CRB26.5x24 HIGH vented

• HINGE KIT - Standard Hinge kit for exhaust fan roof curbs. Includes Hardware to attach hinge to

curb and hinge to base. Ships Loose. Used on Fans with wheels 20 inches or smaller. 12 GA

Galvanized.

 

(MUA-1)

FKH2-D.250-20D Direct Gas Fired Heated Make Up Air Unit with 20" Mixed Flow

Direct Drive Fan

Supply Fan handles 4781 CFM @ 0.500" wc ESP, Fan runs at 1742 RPM.

Heater supplies 242890 BTUs. 48°F Temperature Rise. [Fuel: Natural Gas]

Supply Motor: 5.000 HP, 3 Phase, 208 V, 60Hz, 15.0 FLA, ODP, Premium (EPlus3)

Eff.

Down Discharge - Air Flow Right -> Left

Intake:

Sloped Filtered Intake Hood with EZ Filters

Gas type:

Natural

Temperature control option:

0-150°F Discharge Temp Control • Heating Activation Based On Intake Set Point • Manual Blower

Mode. Includes Remote HMI. Use with MUA

Curb:

FKH2 - 31"Wide x 79" Long x 20" High • Insulated

Included options:

• VERIZON CELLULAR KIT, WIRED ANTENNA AND VERIZON DATA FOR 1 YEARS. USED WITH FAN

•Pilot located upstream of First Redundant Solenoid Valve Max Gas Pressure of 14" wc.

•Motorized Back Draft Damper for Standard & Modular Direct Fired Heaters w/Extended Shaft,

Standard Galvanized Construction, 3/4" Rear Flange, LF120S Actuator Included

•Freezestat With 10' Sensor. Factory set at 35°F and 10 minutes.

•Pre purge (set at 30 seconds) allowing the blower to purge the inside of the heater

•Low Fire Start. Allows the burner circuit to energize when the modulation control is in a low fire

position.

•Separate 120VAC Wiring Package for Make-Up Air Units. Option must be selected when mounting

VFD in prewire panel or with DCV package. Provides separate 120VAC input to supply fan. This

120V signal must be run by electrician from DCV to mua switch.

 

1 X ECP

SC-32111002 3 Phase w/ control for 2 Exhaust Fans, 1 Supply Fan, Exhaust on in

Fire, Lights out in Fire. INVERTER DUTY 3 PHASE MOTOR REQUIRED FOR USE

WITH VFD.

- ESV751N02YXB571 - Variable Frequency Drive - 1 HP Max., 200/240 V, Single

or Three Phase Input, 4.2 A Max., NEMA 1 Enclosure, with 2RJ-45 FOR MODBUS

- ESV222N02YXB571 - Variable Frequency Drive - 3 HP Max., 200/240 V, Single

or Three Phase Input, 9.6 A Max., NEMA 1 Enclosure, with 2RJ-45 FOR MODBUS

- ESV402N02TXB571 - Variable Frequency Drive - 5 HP Max., 200/240 V, Three

Phase, 16.5 A Max., NEMA 1 Enclosure, with 2RJ-45 FOR MODBUS

- 20 wide X18 tall X8.62 deep SS HINGED ELECTRICAL BOX NEMA 1 - VENTED.

Stainless plate instead of filter assembly.

- Digital Prewire Lighting Relay Kit. Includes hood lighting relay & terminal blocks.

Allows for up to 1400W of lighting each.

 

*QUOTE IS VALID FOR 30 DAYS*

EXCLUSIONS

  • CUTTING, CORING,SCANNING, XRAY, FIRESTOP
  • ARIEL LIFT PLATFORM IF REQUIRED
  • ROOF AND WALL PENETRATIONS AND SEALING
  • CLEARANCE REDUCTION PANELS TO BE DONE BY STAINLESS CONTRACTOR
  • SEISMIC ENGINEERING TO BE DONE BY GENERAL CONTRACTOR
  • ACOUSTIC INSULATION INCLUDED, ALL OTHERS WILL BE DONE AT AN ADDITIONAL CHARGE
Hrs/Qty Service Rate/PriceAdjustSub Total
1 KITCHEN EQUIPTMENT PACKAGE $105,800.000.00%$105,800.00
Sub Total $105,800.00
GST $5,290.00
Total $111,090.00